5 Technical Background on RS485
5.3 Polarization
In RS485 the sender must activate the transmitter before sending data, and deactivate it when all
data is sent. At times when no devices send data all transmitters are inactive. As the result the
data lines are floating, and the differential voltage is undefined. It may happen the next data is
not correctly recognized, because the change from undefined to data signals is not detected.
To avoid such problems the data lines should be polarized by resistors. These insure the differential
voltage to be above +200mV. Typically the positive line is pulled to +5V, while the negative line is
pulled to GND. When Termination Resistors are applied, the voltage on these must be +200mV or
above. When the termination resistors are of the 120Ω types, the polarization resistors shall have
about 750 to 1000Ω.
The Polarization Resistors must not be too small, because they add current to the signals, and a
transmitter has to act against that. A typical transmitter provides up to 60 mA of current in high
and low level.
5.4 2-Wire Scheme
In many configurations a very simple cabling is required. RS485 allows for so called 2-wire cabling
as shown below. Several devices are connected in parallel to the wires, which is called bus topology.
Each device can either send own or receive foreign data at a given time, so it is operating in
half-duplex mode.
Shown in figure 24 are three devices, RS485 specifies up to 32. The data lines are named as Data+
and Data-, a positive differential voltage is the state for a transmitted One. The GND is also
connected between all devices as required, so the cabling is 3-wire in reality.
Figure 24: 2-wire cabling scheme
The resistors P1 and P2 are for polarization, T1 and T2 are for the termination function. Polar-
ization of Data+ and Data- appears only once on this net, the termination is at the physical ends
of the cable.
All devices appear the same on the cable, they have the same function. There is no Master or
Slave defined by the hardware. Such functions are implemented by way of the data transmission
protocol. Also RS485 addresses are defined by that protocol, as well as bus access.
June 2009 USB-COM PRO User Manual 28
Seitenansicht 27
1 2 ... 23 24 25 26 27 28 29 30 31

Kommentare zu diesen Handbüchern

Keine Kommentare

Carlon Duct Proofing and Cable manuali

Manuali dei proprietari e guide per l'utente per Apparecchiature Carlon Duct Proofing and Cable.
We fornisce 1 manuali pdf Carlon Duct Proofing and Cable per scaricare gratuitamente in base al tipo di documento: Manuale Utente


Carlon Duct Proofing and Cable Manuale Utente (3 pagine)


Marchio: Carlon | Categoria: Equipment | Dimensione: 0.07 MB |

 

Indice





Più prodotti e manuali per Apparecchiature Carlon

Modelli Tipo di Documento
E-Loc Manuale Utente   Carlon E-Loc User Manual, 1 pagine
Drop-In Floor Box Manuale Utente   Carlon Drop-In Floor Box User Manual, 2 pagine
Expansion Joints for PVC Rigid Nonmetallic Conduit Manuale Utente   Carlon Expansion Joints for PVC Rigid Nonmetallic Conduit User Manual, 6 pagine
External Load Calculation for Buried Conduit Manuale Utente   Carlon External Load Calculation for Buried Conduit User Manual, 7 pagine
Expansion Joints Manuale Utente   Carlon Expansion Joints User Manual, 6 pagine
Intra-Gard - Low Res Manuale Utente   Carlon Intra-Gard - Low Res User Manual, 2 pagine
Multi-Gard Fiberglass Product Description Manuale Utente   Carlon Multi-Gard Fiberglass Product Description User Manual, 6 pagine
White Adjustable Floor Box Kit - Low Res Manuale Utente   Carlon White Adjustable Floor Box Kit - Low Res User Manual, 4 pagine
Multi-Gard Galvanized Steel Product Description Manuale Utente   Carlon Multi-Gard Galvanized Steel Product Description User Manual, 3 pagine
Multi-Gard Installation Procedures Manuale Utente   Carlon Multi-Gard Installation Procedures User Manual, 7 pagine
P&C Duct and Telephone Duct Expansion and Cont Manuale Utente   Carlon P&C Duct and Telephone Duct Expansion and Contraction - Low Res User Manual, 1 pagine
Multi-Gard PVC Product Description Manuale Utente   Carlon Multi-Gard PVC Product Description User Manual, 9 pagine
P&C Duct and Telephone Duct Installation Pract Manuale Utente   Carlon P&C Duct and Telephone Duct Installation Practices - Low Res User Manual, 1 pagine
P&C Flex - Low Res Manuale Utente   Carlon P&C Flex - Low Res User Manual, 1 pagine
PVC Conduit Painting Manuale Utente   Carlon PVC Conduit Painting User Manual, 1 pagine
PV Mold Manuale Utente    Carlon PV Mold Manuel d'utilisation, 2 pagine
P&C Flex and HDPE Manuale Utente   Carlon P&C Flex and HDPE User Manual, 4 pagine
Structured Cable Management Systems Handbook - Low Manuale Utente   Carlon Structured Cable Management Systems Handbook - Low Res User Manual, 92 pagine
Rectangular Floor Box, Activation Kit, and Covers Manuale Utente   Carlon Rectangular Floor Box, Activation Kit, and Covers User Manual, 4 pagine
Rigid Nonmetallic Conduit Corrision Resistance - L Manuale Utente   Carlon Rigid Nonmetallic Conduit Corrision Resistance - Low Res User Manual, 1 pagine